Model |
MG750TL |
MG1KTL |
MG1K5TL |
MG2KTL |
MG3KTL |
DC input parameter |
Maximum DC input power (W) |
900 |
1200 |
1700 |
2200 |
3300 |
Maximum DC input voltage (V) |
400 |
450 |
500 |
Starting voltage (V) / minimum operating voltage (V) |
60/50 |
80/60 |
MPPT range (V) |
50-400 |
60-400 |
80-410 |
100-410 |
120-450 |
MPPT number / |
1/1 |
Each group MPPT can access group string number |
Each group has MPPT maximum input current (A) x |
8×1 |
9×1 |
10×1 |
12×1 |
15×1 |
MPPT number |
DC switch |
Optional |
AC output parameter |
Rated output power (W) |
750 |
1000 |
1500 |
2000 |
3000 |
Maximum AC output current (A) |
3.6 |
4.5 |
6.5 |
9 |
13 |
Grid voltage range |
230/180~277V |
Frequency range of power grid |
50Hz(44~55Hz) / 60Hz(54~65Hz) |
Power factor |
≥0.99(rated power) |
Harmonic distortion |
< 3% (rated power) |
AC output |
1PH(L, N, PE) |
System |
Cooling method |
Natural cooling |
Maximum efficiency |
96.80% |
96.90% |
97.20% |
97.20% |
97.30% |
European efficiency |
95.95% |
96.00% |
96.10% |
96.10% |
96.50% |
MPPT efficiency |
99.90% |
Protection level |
IP65 |
Night power consumption (W) |
<1 |
Topology |
No transformer |
Operating ambient temperature |
-25℃~+60℃(auto derating if 45℃ is exceeded) |
Relative humidity |
0~95%,no condensation |
Protection function |
Photovoltaic array insulation impedance protection, photovoltaic array leakage current protection, ground fault monitoring, power grid monitoring |
Island protection, DC monitoring, short-circuit protection, etc. |
Display and communication |
Display |
LED display / LCD (optional) |
LCD language |
English, Chinese, German, Dutch |
Communication mode |
RS485(standard);WiFi, Ethernet (optional) |
Mechanical parameter |
Volume (H, x, W, x, D, mm) |
280x300x138 |
Weight (kg) |
≤9.5 |
Installation method |
Wall installation |
Others |
DC input terminal |
MC4 |
Grid-connected standard |
DIN VDE 0126-1-1:2013,VDE-AR-N 4105:2011,DIN VDE V 0124-100:2012, |
EN 50438:2013,G83-2 :2012,IEC 61727(IEC62116),AS/NZS 4777.2:2015, |
NB/T32004-2013,IEC 60068-2-1:2007,IEC 60068-2-2:2007,IEC 60068-2-14:2009, |
IEC 60068-2-30:2005,IEC 61683:1999,C10/11,TF3.2.1 |
Safety certification / EMC level |
IEC 62109-1 :2010,IEC 62109-2 :2011,EN 61000-6-2: 2005, |
EN 61000-6-3:2007/A1:2011 |
Warranty (year) |
5 |